How should I wire the power and control circuits? Jul 24
  • Power wiring: Use properly sized cables for line, load, and ground. Keep them as short as possible. Separate power and control cables by at least 200 mm to avoid electromagnetic interference.
  • Control wiring: Use shielded twisted-pair cables for analog setpoint and communication signals. Ground the shield only at one end (typically the controller side).
  • Grounding: The SCR unit must be solidly connected to the safety earth (PE). The load’s metal frame must also be grounded.

Always follow the installation diagrams in the specific product manual.